Power and Lighting Device Placement Guide By Building Type

5. Residential

In homes the NEC drives the receptacle count (the 6 ft / 12 ft rule) and requires switched lighting in nearly every room; lighting placement itself is design.

Space
Power
Switching
Lighting
Living rooms and bedrooms
No point on a wall's floor line more than 6 ft from a receptacle; 12–18 in to center
Switch at each entry; 3-way for two entries
Downlights 4–6 ft apart; sconces or switched receptacles for lamps
Kitchens
Counter receptacles so no point is more than 24 in from one; at least two 20 A circuits; GFCI; no more than 20 in above the counter
Separate switches for ceiling, under-cabinet and pendants
Downlights over counter fronts; under-cabinet strips; island pendants 30–36 in above the counter
Bathrooms
Receptacle within 3 ft of each basin, 20 A, GFCI; none within 3 ft of the tub or shower edge up to 8 ft
No switches in the tub or shower space
Sconces 60–66 in to center each side of the mirror; damp or wet listed fixtures in the shower zone; no pendants or fans there
Hallways and stairs
Receptacle in halls 10 ft or longer
3-way at each end of halls; switch at each level for stairs with six or more risers
Fixture about every 8–10 ft; light each landing
Garages
GFCI; one per vehicle bay, no higher than 5½ ft; EV circuit
Switch at each door
Surface LED fixtures over parking spaces and benches
Outdoors
Front and back receptacles no higher than 6½ ft above grade; GFCI, WR, in-use covers
Switch inside each entry; photocell or timer
Entry lanterns about 66 in to center; path lights 6–8 ft apart
Closets
None required
Switch outside the door or a jamb switch
Enclosed LED or fluorescent fixtures with NEC 410.16 clearances

Other residential requirements:

  • Laundry: at least one receptacle on a 20 A circuit, GFCI protected.
  • Foyers over 60 sq ft: a receptacle on each wall 3 ft or wider.
  • Basements and accessory buildings: at least one receptacle in each unfinished area, GFCI protected; switched lighting at the point of entry where used for storage or containing equipment.
  • HVAC equipment: a receptacle within 25 ft of the equipment.
  • Dining rooms: chandelier or pendant bottom 30–36 in above the table; any wall space 2 ft or wider counts toward the receptacle rule.
  • 2026 NEC changes: switched receptacles no longer count toward required receptacles; built-in desks may need receptacles; receptacles below kitchen counters must be at least 24 in below the surface.

6. Commercial and retail

Retail power and lighting follow the merchandising plan; codes add show-window, sign and GFCI rules, while energy codes put lighting on schedules rather than public switches.

Space
Power
Switching
Lighting
Sales floor
Floor boxes or column receptacles where displays move; perimeter at 12–18 in
Lighting control panel on a store schedule; staff override keypad only
Ambient grid spaced about equal to mounting height; track accents at about 30°
Show windows
One receptacle per 12 linear ft, within 18 in of the top of the window
Scheduled with display lighting
Track or adjustable downlights aimed at displays
Entrances
One 20 A sign outlet at each pedestrian entrance
Signage on a time clock
Canopy downlights; exit signs above doors
Cash wraps
Dedicated circuits; isolated-ground where specified
Pendants or downlights over the counter
Back of house
Cleaning receptacles about every 50 ft
Occupancy sensors or switches at each entry
Strips over aisles between shelving
Restaurants
GFCI throughout kitchens and serving areas; matched NEMA receptacles for equipment
Scene keypads in the dining room
Pendants 30–36 in above tables; kitchen fixtures listed for the location
Rooftops and exterior
Receptacle within 25 ft of HVAC equipment; GFCI, WR
Photocell, time clock and contactor
Pole spacing 4–5 times pole height; full-cutoff optics

7. Office

Offices are laid out from the furniture plan: power and task light go where people sit, sensors and schedules run the general lighting, and energy codes require part of the receptacles to switch off automatically.

Space
Power
Switching
Lighting
Open office
Furniture feeds, power poles or floor boxes; one or two circuits per 4–6 workstations
Zone keypads at entries; ceiling occupancy and daylight sensors
Troffers on an 8–10 ft grid or pendants at least 8 ft above the floor; 30–50 fc on desks
Private offices
One duplex per wall, two at the desk wall; part on automatic control
Vacancy sensor with dimmer at the door, top no higher than 48 in
One or two fixtures over the work zone, not behind monitors
Conference rooms (up to 1,000 sq ft)
Wall receptacles by the 6 ft / 12 ft count, placed anywhere; one floor receptacle per 215 sq ft in rooms at least 12 ft wide
Multi-scene keypad at the door, second at the presenter end
Pendant over the table 30–36 in above it; separate presentation-wall zone
Break and copy rooms
GFCI within 6 ft of sinks; dedicated appliance and copier circuits
Occupancy or vacancy sensor
Troffers plus under-cabinet strips
Corridors and lobbies
Cleaning receptacles about every 50 ft
Scheduled; key switch or keypad override at reception
Fixtures every 8–10 ft; pendants above 80 in clear headroom
IT and electrical rooms
Dedicated and locking receptacles for racks
Switch at the entry
Strips over rack aisles

8. School

Schools add tamper-resistant receptacles throughout, emergency shutoffs in labs and shops, and controls students cannot switch off.

Space
Power
Switching
Lighting
Classrooms
TR receptacles every 6–10 ft on perimeter walls; quads and AV power at the teaching wall; charging-cart circuits
Vacancy sensor with multi-button keypad at the door; second keypad at the teaching wall
Pendant rows 8–10 ft apart, parallel to the teaching wall; whiteboard row 2–4 ft from the board
Science labs
GFCI within 6 ft of sinks; bench circuits through a teacher-reachable shutoff
Lighting keypad at the door; emergency power-off at the teacher station
Fixtures over benches, not over fume hoods; wet-listed near sinks
CTE and shop rooms
120 V and 208/240 V machine receptacles with emergency stops
Emergency stops at the teacher station and exits
High output over machines; guarded fixtures
Gyms
TR; recessed or guarded receptacles; floor boxes for events
Key switch or keypad in a staff alcove
High-bays with wire guards at 1–1.5 times mounting height
Auditoriums
TR; stage and AV power
House-light keypads at entries; theatrical console
House downlights on dimmers; aisle and step lights
Corridors
TR; cleaning receptacles about every 50 ft
Scheduled; key switch overrides near the office
Vandal-resistant fixtures every 8–12 ft
Restrooms
GFCI; TR
Ceiling occupancy sensors only
Vandal-resistant fixtures; light the mirror from the front

9. Code quick reference

The hard limits that apply across all four building types.

Device
Limit
Reference
Controls and receptacles in accessible spaces
Operable part 15–48 in above the floor; 44 in over counters deeper than 20 in
ADA 308
Switches
Handle grip no higher than 6 ft 7 in; none in tub or shower spaces; neutral at most switch locations
NEC 404.8, 404.4(C), 404.2(C)
Switches over 300 V apart in one box
Barriers between devices
NEC 404.8(B)
Receptacles near tubs and showers
None within 3 ft horizontally of the edge, up to 8 ft above the rim
NEC 406.9(C)
Receptacles near sinks and in wet areas
GFCI within 6 ft of sinks, tubs and showers, and in kitchens, baths, outdoors and garages
NEC 210.8
Countertop receptacles
No face-up receptacles unless listed; island side receptacles do not count toward the countertop requirement
NEC 406.5, 210.52(C)
Tamper-resistant receptacles
Required in dwellings, schools, childcare, hotels and similar; not above 5½ ft
NEC 406.12
Fixtures in the tub and shower zone
No pendants, track, cord-connected fixtures or fans within 3 ft horizontally and 8 ft vertically; others listed damp or wet
NEC 410.10(D)
Closet fixtures
No open-lamp incandescent or pendants; 12 in clearance (surface) or 6 in (recessed) from storage space
NEC 410.16
Recessed fixtures in insulation
IC-rated, or 3 in from insulation and ½ in from combustibles
NEC 410.116
Headroom and protruding fixtures
80 in clear over walkways; wall fixtures between 27 and 80 in project no more than 4 in
ADA 307
Egress lighting
1 fc minimum on normal power; on emergency power, 1 fc average and 0.1 fc minimum
IBC 1008, NFPA 101

Sources

Typical heights, spacing and layout practice are from general industry and IES practice; confirm with the adopted codes and project-specific calculations.