Power and Lighting Device Placement Guide - Offices

Offices are laid out from the furniture plan: power and task light go where people sit, sensors and schedules run the general lighting, and energy codes require part of the receptacles to switch off automatically.

Space
Power
Switching
Lighting
Open office
Furniture feeds, power poles or floor boxes; one or two circuits per 4–6 workstations
Zone keypads at entries; ceiling occupancy and daylight sensors
Troffers on an 8–10 ft grid or pendants at least 8 ft above the floor; 30–50 fc on desks
Private offices
One duplex per wall, two at the desk wall; part on automatic control
Vacancy sensor with dimmer at the door, top no higher than 48 in
One or two fixtures over the work zone, not behind monitors
Conference rooms (up to 1,000 sq ft)
Wall receptacles by the 6 ft / 12 ft count, placed anywhere; one floor receptacle per 215 sq ft in rooms at least 12 ft wide
Multi-scene keypad at the door, second at the presenter end
Pendant over the table 30–36 in above it; separate presentation-wall zone
Break and copy rooms
GFCI within 6 ft of sinks; dedicated appliance and copier circuits
Occupancy or vacancy sensor
Troffers plus under-cabinet strips
Corridors and lobbies
Cleaning receptacles about every 50 ft
Scheduled; key switch or keypad override at reception
Fixtures every 8–10 ft; pendants above 80 in clear headroom
IT and electrical rooms
Dedicated and locking receptacles for racks
Switch at the entry
Strips over rack aisles