Power and Lighting Device Placement Guide - Schools

Schools add tamper-resistant receptacles throughout, emergency shutoffs in labs and shops, and controls students cannot switch off.

Space
Power
Switching
Lighting
Classrooms
TR receptacles every 6–10 ft on perimeter walls; quads and AV power at the teaching wall; charging-cart circuits
Vacancy sensor with multi-button keypad at the door; second keypad at the teaching wall
Pendant rows 8–10 ft apart, parallel to the teaching wall; whiteboard row 2–4 ft from the board
Science labs
GFCI within 6 ft of sinks; bench circuits through a teacher-reachable shutoff
Lighting keypad at the door; emergency power-off at the teacher station
Fixtures over benches, not over fume hoods; wet-listed near sinks
CTE and shop rooms
120 V and 208/240 V machine receptacles with emergency stops
Emergency stops at the teacher station and exits
High output over machines; guarded fixtures
Gyms
TR; recessed or guarded receptacles; floor boxes for events
Key switch or keypad in a staff alcove
High-bays with wire guards at 1–1.5 times mounting height
Auditoriums
TR; stage and AV power
House-light keypads at entries; theatrical console
House downlights on dimmers; aisle and step lights
Corridors
TR; cleaning receptacles about every 50 ft
Scheduled; key switch overrides near the office
Vandal-resistant fixtures every 8–12 ft
Restrooms
GFCI; TR
Ceiling occupancy sensors only
Vandal-resistant fixtures; light the mirror from the front

9. Code quick reference

The hard limits that apply across all four building types.

Device
Limit
Reference
Controls and receptacles in accessible spaces
Operable part 15–48 in above the floor; 44 in over counters deeper than 20 in
ADA 308
Switches
Handle grip no higher than 6 ft 7 in; none in tub or shower spaces; neutral at most switch locations
NEC 404.8, 404.4(C), 404.2(C)
Switches over 300 V apart in one box
Barriers between devices
NEC 404.8(B)
Receptacles near tubs and showers
None within 3 ft horizontally of the edge, up to 8 ft above the rim
NEC 406.9(C)
Receptacles near sinks and in wet areas
GFCI within 6 ft of sinks, tubs and showers, and in kitchens, baths, outdoors and garages
NEC 210.8
Countertop receptacles
No face-up receptacles unless listed; island side receptacles do not count toward the countertop requirement
NEC 406.5, 210.52(C)
Tamper-resistant receptacles
Required in dwellings, schools, childcare, hotels and similar; not above 5½ ft
NEC 406.12
Fixtures in the tub and shower zone
No pendants, track, cord-connected fixtures or fans within 3 ft horizontally and 8 ft vertically; others listed damp or wet
NEC 410.10(D)
Closet fixtures
No open-lamp incandescent or pendants; 12 in clearance (surface) or 6 in (recessed) from storage space
NEC 410.16
Recessed fixtures in insulation
IC-rated, or 3 in from insulation and ½ in from combustibles
NEC 410.116
Headroom and protruding fixtures
80 in clear over walkways; wall fixtures between 27 and 80 in project no more than 4 in
ADA 307
Egress lighting
1 fc minimum on normal power; on emergency power, 1 fc average and 0.1 fc minimum
IBC 1008, NFPA 101