Circuiting decides which outlets, lights and equipment share a breaker, how many circuits each panel needs, and how panels are fed. It works in two directions:
- branch circuits group endpoints back to a nearby panel
- feeders carry power from that panel back to the main panel
Note: This overview is based on US practice — code references follow the model 2023 NEC. The 2026 NEC moved most load-calculation rules from Article 220 to new Article 120 with similar content; confirm the edition your jurisdiction has adopted. Wire sizes assume copper conductors with 75°C terminations.
1. The circuit hierarchy
Feeders run from panel to panel; branch circuits run from the last panel to the endpoints. Each feeder or branch circuit starts at a breaker sized to protect its own wire.

Level | What it is | Protection |
Main panel or switchboard | Receives the service; feeds subpanels and large loads | Main breaker or service disconnect |
Feeder | Conductors from one panel to another | Breaker in the upstream panel |
Subpanel | Panel near the loads it serves | Its own main breaker or lugs protected upstream |
Branch circuit | Conductors from the last breaker to the endpoints | Branch breaker, 15–50 A typically |
Endpoint | Receptacle, fixture or hardwired equipment | Device ratings must match the circuit |
2. Core circuiting rules
Every circuit is sized so its wire, breaker and devices match, its continuous load stays under 80% of the breaker, and its voltage drop stays small.
Breaker, wire and device sizes (copper, 75°C terminations)
Breaker | Minimum wire | Receptacles allowed | Typical loads |
15 A | 14 AWG | 15 A | Residential lighting and general receptacles |
20 A | 12 AWG | 15 A or 20 A | Kitchen, bath, laundry and garage circuits; commercial lighting and receptacles |
30 A | 10 AWG | 30 A only | Dryers, water heaters, small HVAC units |
40–50 A | 8–6 AWG | 40–50 A only | Ranges, EV chargers, heat pumps |
60 A and up | 6 AWG and larger | Hardwired or matching receptacle | Subpanel feeders, large equipment |
Sizing rules
- Continuous loads (3 hours or more): size the breaker and wire for 125% of the continuous load plus 100% of the non-continuous load. In practice a 20 A circuit carries no more than 16 A (1,920 VA at 120 V) of continuous load such as commercial lighting.
- Equipment share of a circuit: on a 15 or 20 A circuit, one cord-and-plug item may draw no more than 80% of the circuit rating, and fastened-in-place equipment no more than 50% where the circuit also serves lights or other receptacles (NEC 210.23).
- Receptacle loads (non-dwelling): count each single or duplex receptacle yoke at 180 VA. A 20 A, 120 V circuit (2,400 VA) therefore holds up to 13 receptacles by calculation; designers typically use 6–10.
- Voltage drop: the NEC recommends, but does not require, no more than 3% on a branch circuit or feeder and 5% total. Long runs often need wire one or two sizes larger than ampacity alone requires.
- Multiwire branch circuits: two or three circuits may share a neutral if their breakers are handle-tied or common-trip, so all are switched off together.
- Neutral at each circuit: the neutral and equipment grounding conductor run with their own circuit's conductors.
Load calculation basis (2023 NEC Article 220)
Occupancy | General lighting load | Receptacle load |
Dwelling units | 3 VA per sq ft (covers lighting and general receptacles) | Plus 1,500 VA per small-appliance and laundry circuit |
Offices | About 1.3 VA per sq ft | 180 VA per receptacle or 1 VA per sq ft, whichever is greater |
Schools | About 1.5 VA per sq ft | 180 VA per receptacle |
Retail stores | About 1.9 VA per sq ft | 180 VA per receptacle; show windows 200 VA per linear ft |
Warehouses | About 0.3 VA per sq ft | 180 VA per receptacle |
Non-dwelling receptacle loads take a demand factor: the first 10 kVA at 100% and the rest at 50%. Lighting values for offices, schools, retail and warehouses are from the 2026 NEC table, which has already factored in 125% for continuous load (Open Exam Prep); energy-code lighting power limits are usually lower than these.
3. Residential unit circuiting
The NEC requires dedicated 20 A circuits for four areas of a home: kitchen countertops, bathrooms, laundry and garages. Everything else is designed by load, with practical limits on how many outlets share a circuit.
3.1 Kitchens
Kitchens need the most circuits in the house: at least two for countertop receptacles plus one for each major appliance.
Circuit | Rating | Code basis | Serves |
Small-appliance circuits (at least two) | 20 A, 120 V, 12 AWG; GFCI and AFCI | NEC 210.11(C)(1), 210.52(B) | Countertop receptacles, plus wall receptacles in the kitchen, pantry, breakfast area and dining room; no lighting, and no outlets in other rooms |
Refrigerator | 15–20 A, 120 V | Permitted as an individual circuit (210.52(B) exception) | Refrigerator only; recommended, not required |
Electric range or cooktop | 40–50 A, 240 V, 8–6 AWG | Sized to the nameplate | Range, or a cooktop and wall oven on separate circuits |
Dishwasher | 15–20 A, 120 V; GFCI | Dedicated by manufacturer instructions | Dishwasher |
Disposal | 15–20 A, 120 V | Dedicated by manufacturer instructions; may share with the dishwasher if the load allows | Disposal |
Microwave (built-in or over-range) | 20 A, 120 V | Dedicated by manufacturer instructions | Microwave or microwave/hood combination |
Range hood (separate) | 15–20 A, 120 V | By load | Hood fan and light |
Kitchen lighting | 15 A, 120 V; AFCI | Not dedicated | May share with other rooms' lighting |
Countertop receptacles must be fed from at least two circuits so two high-wattage appliances (a kettle and a toaster, say) can run at once. Alternating circuits between adjacent countertop receptacles spreads the load.
3.2 Bathrooms
Option | Rule | Practice |
One 20 A circuit for several bathrooms | Serves bathroom receptacles only; no lights, fans or other outlets | Common in small homes |
One 20 A circuit per bathroom | May also serve that bathroom's lighting, exhaust fan and other equipment in the same room | Preferred; avoids tripping when hair dryers run in two baths |
Heated floors, towel warmers, heaters | Separate circuits sized to the load | Often 15–20 A dedicated; GFCI per manufacturer |
Whirlpool tubs and steam showers | Individual circuits sized to the nameplate; GFCI | Per NEC Article 680 and manufacturer |
All bathroom receptacles need GFCI protection. Bathroom circuits are not required to have AFCI protection.
3.3 Bedrooms and living areas
Bedrooms have no dedicated-circuit requirement; they are circuited by load, with typical practice of 8–10 outlets per 15 A circuit or 10–12 per 20 A circuit (outlets include lights).
- AFCI: every 15 and 20 A, 120 V circuit serving bedrooms, living rooms, family and dining rooms, closets, hallways and similar rooms needs AFCI protection.
- Separate lighting and receptacles: many designers put each bedroom's receptacles on one circuit and group lighting from several rooms on another, so a tripped receptacle circuit does not leave the room dark.
- Dedicated loads: window or wall air conditioners, space heaters, home offices with heavy equipment, and media walls warrant their own circuits.
- Smoke alarms: hardwired, interconnected alarms with battery backup, usually on a regularly used lighting circuit so a tripped breaker is noticed quickly.
3.4 Laundry rooms
Circuit | Rating | Code basis | Serves |
Laundry receptacle circuit | 20 A, 120 V, 12 AWG; GFCI and AFCI | NEC 210.11(C)(2) | Laundry receptacles, including the washer; no other outlets |
Electric dryer | 30 A, 240 V, 10 AWG, 4-wire NEMA 14-30R | Sized to the nameplate | Dryer only |
Heat-pump dryer | Often 15–20 A, 120 V or 240 V | Per manufacturer | Dryer only |
Laundry lighting | 15 A, 120 V; AFCI | Not dedicated | May share with other lighting |
3.5 Other required and recommended circuits
Circuit | Rating | Code basis |
Garage receptacles | At least one 20 A circuit serving only the garage (and exterior outlets) | NEC 210.11(C)(4) |
Water heater (electric resistance) | 30 A, 240 V for a typical 4.5 kW element; heat-pump models often 15–30 A | Nameplate |
HVAC (furnace, air handler, heat pump, AC condenser) | Sized from the nameplate's minimum circuit ampacity and maximum overcurrent protection | NEC 440 |
EV charger | 40–60 A, 240 V for Level 2 | Nameplate; continuous load at 125% |
Outdoor receptacles | GFCI; often on their own 20 A circuit | NEC 210.8(A) |
Sump, well and sewage pumps | Dedicated, sized to the motor | Nameplate |
3.6 Example panel schedule
A typical all-electric three-bedroom, two-bath home on a 200 A, 120/240 V service. Spaces are numbered in sequence for clarity (real panels number odd on the left and even on the right); a two-pole breaker takes two spaces. Ratings are illustrative and must come from the load calculation and nameplates.
Spaces | Breaker | Wire (Cu) | Serves | Protection |
1 | 20 A | 12 AWG | Kitchen countertop receptacles (west) | GFCI + AFCI |
2 | 20 A | 12 AWG | Kitchen countertop receptacles (east) and dining room | GFCI + AFCI |
3 | 20 A | 12 AWG | Refrigerator | AFCI |
4 | 20 A | 12 AWG | Dishwasher | GFCI + AFCI |
5 | 20 A | 12 AWG | Disposal | AFCI |
6 | 20 A | 12 AWG | Built-in microwave / hood | AFCI |
7–8 | 50 A, 2-pole | 6 AWG | Electric or induction range | Per range listing |
9 | 20 A | 12 AWG | Primary bath: receptacles, light and fan | GFCI |
10 | 20 A | 12 AWG | Hall bath: receptacles, light and fan | GFCI |
11 | 20 A | 12 AWG | Laundry receptacles and washer | GFCI + AFCI |
12–13 | 30 A, 2-pole | 10 AWG | Electric dryer | GFCI |
14 | 15 A | 14 AWG | Bedroom 1 receptacles and lighting | AFCI |
15 | 15 A | 14 AWG | Bedrooms 2 and 3 receptacles | AFCI |
16 | 15 A | 14 AWG | Bedrooms 2 and 3 lighting, hall, smoke alarms | AFCI |
17 | 20 A | 12 AWG | Living room receptacles | AFCI |
18 | 15 A | 14 AWG | Living, dining, entry and kitchen lighting | AFCI |
19 | 20 A | 12 AWG | Garage and outdoor receptacles | GFCI |
20–21 | 50 A, 2-pole | 6 AWG | Level 2 EV charger (40 A continuous) | GFCI if receptacle-connected |
22–23 | 30 A, 2-pole | 10 AWG | Heat-pump water heater or 4.5 kW tank | Per nameplate |
24–25 | 40 A, 2-pole | 8 AWG | Heat pump outdoor unit (per nameplate) | Per NEC 440 |
26–27 | 60 A, 2-pole | 6 AWG | Air handler with backup heat strips (per nameplate) | Per nameplate |
28 | 15 A | 14 AWG | Garage and exterior lighting | |
29–40 | Spare spaces for future loads |
GFCI on 240 V circuits reflects the 2023 NEC's coverage of 125–250 V receptacles in kitchens, laundry areas, garages and outdoors; hardwired equipment and local amendments vary, so confirm with the adopted code.
Circuit lists for kitchens, bathrooms, laundry and garages, and AFCI and GFCI locations: Open Exam Prep.
4. Circuiting endpoints to subpanels
Branch circuits connect endpoints (receptacles, lights, equipment) back to the nearest panel. Good circuiting groups outlets so that one tripped breaker affects as little as possible, loads stay under 80% of the breaker, and wiring runs stay short.
Grouping strategies
Strategy | How it works | Where it fits |
By room | One circuit per room or pair of rooms | Homes, private offices, hotel rooms |
By function | Lighting, receptacles and equipment on separate circuits | All building types; required by energy codes for separate metering in many commercial buildings |
By area or zone | One circuit per bay, workstation cluster or classroom wall | Open offices, classrooms, retail floors |
Alternating | Adjacent receptacles on different circuits | Kitchens, conference rooms, labs, so a trip leaves power nearby |
Dedicated | One outlet or machine per circuit | Appliances, HVAC, copiers, EV chargers, IT racks, any motor or heater |
By control zone | Lighting circuits follow switching and sensor zones | Offices and schools under energy codes |
Typical outlets per circuit (practice, not code limits)
Circuit | Typical maximum |
Residential 15 A general purpose | 8–10 outlets |
Residential 20 A general purpose | 10–12 outlets |
Commercial 20 A receptacle | 6–10 duplex receptacles (180 VA each allows 13 by calculation) |
Office workstation circuits | 4–6 workstations per circuit, or per manufacturer for furniture systems |
277 V LED lighting, 20 A | Up to about 4,400 VA continuous (80%), commonly 2,000–3,000 VA to leave spare capacity |
120 V LED lighting, 20 A | Up to about 1,900 VA continuous |
Homeruns and routing
- A homerun is the run from the last box of a circuit back to the panel. Plans show it as an arrow labeled with the panel and circuit number (for example, "LP-2A-14").
- Loop outlets in the order they sit along walls or rows, and bring the homerun from the box closest to the panel.
- Combine up to three circuits in one homerun conduit with a shared neutral (a multiwire branch circuit) only with a handle-tied breaker; otherwise give each circuit its own neutral.
- More than three current-carrying conductors in one raceway or cable bundle triggers ampacity derating, which often forces a larger wire size.
- Keep normal, emergency and low-voltage wiring in separate raceways; emergency (life-safety) circuits must be kept entirely separate from normal wiring.
- Choose panel locations so most branch circuits stay under about 75–100 ft; beyond that, upsize the wire for voltage drop or add a panel closer to the loads.
5. Feeders from remote subpanels to the main panel
A feeder carries power from the main panel (or switchboard) to a subpanel. It is sized from a load calculation of everything the subpanel serves, protected by a breaker at the main panel, and always carries its own equipment grounding conductor.
Sizing and protection
- Ampacity: at least 100% of the non-continuous load plus 125% of the continuous load (NEC 215.2), after demand factors from the load calculation.
- Overcurrent protection: a breaker in the upstream panel sized to protect the feeder conductors; the subpanel's bus rating must equal or exceed it.
- Voltage drop: aim for 2–3% on the feeder so feeder and branch together stay under 5% (recommended, not required).
- Spare capacity: size feeders and subpanels with 20–25% spare capacity and spare breaker spaces for future loads.
- Ground-fault protection: feeder disconnects of 1,000 A or more on 480Y/277 V systems need equipment ground-fault protection (NEC 215.10).
Typical feeder sizes (copper, 75°C, before voltage-drop upsizing)
Feeder breaker | Typical copper conductor | Typical use |
60 A | 6 AWG | Garage, workshop or ADU subpanel |
100 A | 3 AWG | Large garage, small ADU, unit panel in an apartment |
125 A | 1 AWG | Apartment unit panel, small commercial tenant |
200 A | 3/0 AWG | Large unit, floor distribution in a small office |
225 A | 4/0 AWG | Commercial floor or wing panel |
400 A and up | Parallel sets or busway | Risers and main distribution in commercial buildings |
Grounding and neutral separation
- The neutral is bonded to ground in one place only: the service (main) disconnect, or the source of a separately derived system such as a transformer.
- At every subpanel, the neutral bar is isolated from the enclosure and the equipment grounding conductors land on a separate bar bonded to the enclosure. A four-wire feeder (two hots, neutral and ground; or three hots, neutral and ground) is required.
- Each step-down transformer is a new system: bond neutral to ground at the transformer or its first disconnect, and connect it to a grounding electrode.
Remote and separate-building subpanels
- A separate building (detached garage, ADU, pool house, portable classroom) generally gets one feeder, a disconnect at or near where the feeder enters, its own grounding electrode, and a four-wire feeder with the neutral not bonded at the building (NEC 225, 250.32).
- Underground feeders need burial depths and protection per NEC 300.5.
- Long feeders are often upsized for voltage drop; a 100 A feeder over about 150 ft frequently moves up one or two wire sizes.
Feeder sizing, grounding and separate-building rules: Open Exam Prep.
6. Commercial and retail circuiting
Commercial buildings separate circuits by voltage and function: lighting and large mechanical loads at 480Y/277 V, receptacles and small equipment at 208Y/120 V through step-down transformers, and each tenant fed from its own panel and meter.
Load | Typical circuiting | Notes |
General lighting | 277 V, 20 A circuits from the lighting panel, grouped by control zone | Continuous load: keep under 16 A |
Sales floor receptacles | 120 V, 20 A, 6–10 receptacles per circuit | Floor boxes on their own circuits |
Show windows | One receptacle per 12 linear ft; 200 VA per linear ft in the load calculation | Often on a scheduled circuit |
Signs | At least one 20 A circuit for each entrance sign outlet, serving no other load | NEC 600.5 |
Point of sale and cash wraps | Dedicated 20 A circuits; isolated ground where specified | Often on UPS |
Refrigerated cases and walk-ins | Dedicated circuits per case or compressor | Large stores use refrigeration racks on their own panels |
Restaurant kitchen equipment | Dedicated 208 V or 120 V circuits per appliance; GFCI | Shunt-trip to cut power under hoods when the fire system discharges |
Rooftop HVAC | Dedicated 208 V or 480 V, three-phase circuits sized from the nameplate | Service receptacle within 25 ft |
Exterior and parking lighting | 277 V circuits through a contactor on a time clock or photocell | Long runs: check voltage drop |
Emergency lighting | Separate circuits from an emergency panel or unit batteries | Kept in separate raceways |
Panel strategy. A typical retail tenant has one 208Y/120 V panel for receptacles and equipment and, in larger spaces, a 480Y/277 V panel for lighting and HVAC. Each panel is fed from the building's metered distribution section, and the panel schedule labels every circuit by area and load.
7. Office circuiting
Offices circuit by floor and zone: each floor's electrical room holds a 277 V lighting panel and one or more 208Y/120 V receptacle panels fed through a step-down transformer, all fed from a riser.
Load | Typical circuiting | Notes |
Open-office workstations | 4–6 workstations per 20 A circuit through furniture feeds, floor boxes or power poles | Furniture systems often use 3-circuit or 4-circuit 8-wire feeds with shared or dedicated neutrals |
Private offices | One 20 A circuit for 2–4 offices | Separate controlled receptacles under energy codes |
Conference rooms | Dedicated circuit for wall receptacles; separate circuit for floor boxes and AV | Large rooms: AV on its own circuit, often with isolated ground |
Copy and print rooms | Dedicated 20 A circuit per large copier | Some need 208 V or 30 A |
Break rooms | 20 A circuits for counter receptacles; dedicated circuits for refrigerator, microwave, coffee and dishwasher | GFCI within 6 ft of sinks |
IT and telecom rooms | Dedicated circuits per rack, often 208 V, 20–30 A locking receptacles; UPS-backed | Separate panel for large data rooms |
Lighting | 277 V, 20 A circuits following control zones | Daylight zones on separate circuits or controlled channels |
Automatically controlled receptacles | At least half of the receptacles in offices, conference rooms, copy rooms and similar spaces, on circuits that switch off when unoccupied | ASHRAE 90.1 and Title 24 |
Panel strategy. Size each floor's receptacle panel for 20–25% spare capacity, since tenant fit-outs rarely match the base design. Many owners specify separate panels or meters for lighting, receptacles and HVAC so energy use can be tracked by end use, as energy codes increasingly require.
8. School circuiting
Schools circuit by wing and by space type. Each wing has lighting and receptacle panels; labs, shops, kitchens and gyms get their own panels or dedicated circuits with safety shutoffs.
Space | Typical circuiting | Notes |
Classrooms | Two or three 20 A receptacle circuits per room: one or two for perimeter walls, one for the teaching wall and AV; a dedicated circuit for device-charging carts | Tamper-resistant receptacles throughout |
Science labs | Bench receptacles on GFCI circuits fed through a shunt-trip or contactor with an emergency-off button | One circuit per 2–4 student stations |
CTE and shop rooms | Dedicated 120 V and 208/240 V circuits per machine, through a contactor with emergency stops | Often a dedicated shop panel |
Kitchens and cafeterias | Dedicated circuits per appliance; GFCI | Shunt-trip under hoods; usually a kitchen panel |
Gyms and auditoriums | Lighting circuits by zone; dedicated circuits for scoreboards, sound and stage equipment | Stage dimming on its own panel or rack |
Corridors and common areas | 20 A circuits for cleaning receptacles, drinking fountains and displays | |
Emergency and life safety | Egress lighting, fire alarm and PA on emergency panels or generator-backed circuits | Separate raceways |
Portable classrooms | Each fed by its own feeder from the main building to a small panel | Separate-building feeder rules apply |
Panel strategy. Locate panels by wing so classroom circuits stay short, and size feeders for growth in device charging and air conditioning, the two loads most often added to existing schools.
Sources
- Required branch circuits and GFCI/AFCI protection, Open Exam Prep (NEC 210.11, 210.12, 210.8, 210.52)
- Feeders and outside branch circuits, Articles 215 and 225, Open Exam Prep
- Commercial lighting and receptacle load, Open Exam Prep (2026 NEC Article 120)
Wire and breaker pairings, outlets per circuit, typical feeder sizes and building-type practice are from general industry knowledge, not these sources. Size actual circuits and feeders from a load calculation under the adopted code, and have a licensed engineer or electrician confirm them.