Workflow
Creating a Power Circuit
- Select a Receptacle in a Power Plan view or 3D view.
- Open Modify | Electrical Fixtures > Create Systems > Power
- Select the Panel for this power circuit.
- Choose a Panel from the drop-down menu of available panels (already placed in this project) in the System Tools section of the Ribbon.
- Choose the devices to be included in this power circuit.
- Open the Edit Circuit tool.
- Add the devices to this power circuit.
- Click Add to Circuit.
- Select the additional receptacles and devices to be added.
- Note: Circuit requirements
- Click Finish Editing Circuit when done.



Viewing a Power Circuit
- Hover over a receptacle in the power circuit and press Tab once.
- Lines will display the receptacles included in the circuit.
- Click once to select and modify the circuit.
- The Properties Palette displays information about the Electrical Loads on the circuit (based on the receptacles and devices included):
- Connection Type
- Load Name
- Rating (Breaker Size required)
- Voltage
- Apparent Current
- Assuming 1.5 A per receptacle


Converting the Temporary Circuit Lines to Wire
- Hover over a receptacle in the power circuit and press Tab once.
- Lines will display the receptacles included in the circuit.
- Click once to select and modify the circuit.
- Choose the wire style to use from the Convert to Wire section of the ribbon.


AI Prompts

You can download this model file here:
Adding Power Circuits
Prompt | Tool Options
๐ขย = Autodesk Asst
๐ตย = Revit MCP
๐ฃย = Python + Dynamo |
Add power circuits to this residential unit:
โข Create separate power circuits for each room or use to meet all code requirements.
โข Connect all circuits to the electrical panel at the entry.
โข Convert all temporary wires to Arc Wires.
โข Show short 3โ home-run wires from the last devices on each circuit aimed at the panel.
As you work, send me a message after each step saying what you did and what you found. | ๐ฃ |
Tag the circuits with their Load Names | ๐ฃ |
Claude Response
I'll start by checking the open Revit model to find the panel, rooms, and temporary wires before building any circuits.
Now I'll inventory the electrical content: panel, devices, existing circuits and wires.
Revit 2024+ uses .Value instead of .IntegerValue; adjusting.
Step 1 โ Model inventory done. Model "261109 Sample Apartment Electrical System" is open, one level of rooms on L1: Closet, Bath, Bedroom, Living, Kitchen, Entry.
What I found:
- Panel A (208V MLO lighting & appliance panelboard) sits in the Entry.
- 26 receptacles: 8 Bedroom, 7 Living, 1 Entry, 1 GFCI in Bath, 4 GFCI in Kitchen, 2 weatherproof GFCI outside (no room). Plus a Dishwasher with a power connector.
- Existing circuits: A-1 (Entry receptacle) and A-2 (7 of the 8 Bedroom receptacles โ one was missed). Everything else is uncircuited.
- No wires exist yet โ every circuit is only showing as temporary wiring, so the Arc Wire conversion will cover all of them.
- Can't circuit: the Refrigerator and Cooktop families have no electrical connector, so they can't join a circuit as-is. Closet has no devices.
Next: checking panel settings and the electrical plan view, then building the circuits.
Step 2 โ Panel and view check done. Panel A is 225 A MLO, 120/208 V 3-phase wye, 42 spaces, 20 A breakers on the two existing circuits. Its own upstream feed is unconnected (normal for a unit panel with no service modeled). Wiring will go in the L1 - Power plan.
Circuit plan, based on NEC 2023 dwelling requirements:
- A-1 Entry โ keep as is
- A-2 Bedroom โ keep, add the missed receptacle (AFCI)
- Living โ new 20 A (AFCI)
- Kitchen countertop โ two new 20 A small-appliance circuits, GFCI (210.11(C)(1))
- Dishwasher โ new dedicated circuit, GFCI (210.8(D))
- Bath โ new dedicated 20 A, GFCI (210.11(C)(3))
- Exterior โ new 20 A for the two weatherproof GFCI receptacles
Building these now.
Step 3 โ Circuits created. Panel A now has 8 single-pole 20 A, 120 V circuits:
Ckt | Load | Devices |
A-1 | Entry Receptacle | 1 |
A-2 | Bedroom Receptacles | 8 (added the missed one) |
A-3 | Living Receptacles | 7 |
A-4 | Kitchen Countertop SABC 1 | 2 GFCI |
A-5 | Kitchen Countertop SABC 2 | 2 GFCI |
A-6 | Dishwasher (dedicated, 500 VA) | 1 |
A-7 | Bath Receptacle (dedicated) | 1 GFCI |
A-8 | Exterior Receptacles | 2 WR GFCI |
All 24 connectable devices are on a circuit; Bedroom and Living are each under the 13-outlet limit for a 20 A circuit. Next: converting the temporary wiring to Arc Wires in L1 - Power.
Verifying the wires and looking at the plan.
Step 4 โ Arc Wires done and model saved. Created 24 THWN Arc Wires in L1 - Power: each circuit is daisy-chained device to device, ending in a home run toward Panel A in the Entry. Every receptacle and the dishwasher is now wired, no devices are left on temporary wiring, and the model has 0 warnings.
Panel A in the Entry now feeds eight 20 A power circuits, A-1 through A-8, one per room or use, all drawn as Arc Wires in L1 - Power. I saved the model.
A few things you should handle before issue:
- Refrigerator and cooktop aren't circuited. Their families have no electrical connector. If they're electric, swap in families that have connectors. The cooktop then needs a dedicated 2-pole 208 V circuit. A dedicated refrigerator circuit is also good practice.
- No laundry circuit. NEC 210.11(C)(2) requires one, but there's no laundry space in this model. If the unit has one, add it.
- AFCI/GFCI protection isn't recorded in the model. Mark these on the panel schedule or in circuit notes:
- AFCI for Bedroom, Living and Entry
- GFCI for Kitchen countertop, Dishwasher, Bath and Exterior
- Wire paths are auto-generated. The arcs chain each device to its nearest neighbour and end with a home-run arrow near the panel. Some routes cross walls or overlap near the panel, so you may want to tidy them for presentation.
- Panel A has no upstream feed. That's fine if the service isn't modelled yet.