The System Browser gives you a tabular view of every duct-connected component in the model and how each one ties into a system. Before you size ducts, use it to confirm that everything is connected the way you intend and that airflows add up correctly.
Workflow
‣
Opening the System Browser
Press F9, or go to View tab → User Interface → System Browser.
It opens as a dockable pane. Widen it so you can see all the columns.
Keep a 3D view of your ductwork open beside it, zoomed to fit. That way you can see which components you're inspecting.
‣
Setting Up the View
Use the filters at the top to show Systems (rather than Zones).
Set the discipline filter to Mechanical. You can also show All to see how equipment connects across disciplines.
Expand the tree to see the hierarchy:
System classification (Supply Air, Return Air, Exhaust Air)
each named system
the individual components: diffusers, grilles, and air handling units
‣
Reading the Information
Each component row shows key data: airflow (CFM), size, the associated space, and the zone.
Select any row to highlight that element in the model. For example:
Selecting a single supply diffuser shows exactly where it sits.
Selecting an entire supply or return air system highlights everything in it. This makes gaps or stray components easy to spot.
‣
Testing How Loads Roll Up
Change an airflow value on a component, such as a diffuser from 500 to 400 CFM. Watch the system total update in the browser.
Set the value back when you're done.
Use this to:
confirm totals match your design intent.
reallocate air terminals between systems if needed.
If totals don't roll up the way you expect, something probably isn't connected the way you think. That might be a broken duct connection, a fitting that didn't join, or a terminal assigned to the wrong system.
‣
Connecting Equipment to Systems
Your diffusers and grilles should be assigned to a supply, return, or exhaust air system.
Connecting the system to its air handling unit is optional. It can be tricky to get every duct connection to work.
If you do assign the AHU as the system's equipment, it appears in the browser as part of that system.
‣
Understanding the "Unassigned" Section
Any component with a connector that isn't part of a system appears under Unassigned.
This isn't always an error. Equipment often has connectors across several disciplines. For example:
A rooftop AHU can be fully connected to its supply and return air systems.
It will still show as unassigned if its hydronic supply and return, condensate or sanitary drain, or power connectors aren't modeled.
These are fine if you simply haven't modeled those connections.
A diffuser, grille, or other air terminal appearing here usually means a missed connection. Fix it before you move on.
‣
Recommended Workflow Before Duct Sizing
Open the System Browser and filter to Mechanical.
Click through each system and confirm its highlighted extent in 3D matches what you expect.
Check that airflow totals per system are reasonable.
Review the Unassigned section. Separate intentionally unmodeled connectors from real disconnections.
Fix any connection problems. Then proceed to duct sizing.