Using the System Inspector to Review Duct Air Flows
The System Inspector is an on-model analysis tool. It shows airflow, flow direction, static pressure, and pressure loss at each duct segment of a connected system. The System Browser gives you a table of totals. The System Inspector shows how air actually moves through the network, segment by segment.
Workflow
‣
Before You Start
The system must be fully connected. Breaks in the duct network, unjoined fittings, or terminals sitting outside the system will produce incomplete or misleading results. Use the System Browser first to clean these up.
Assign equipment to the system (such as the air handling unit) where possible. This gives the inspector a defined source, so flow direction and the critical path calculate correctly.
Check that calculations are enabled. In the duct system type properties, the Calculations parameter should be set to All. If it's set to None or Flow Only, pressure data won't be available.
Open a view where the ductwork is clearly visible. A 3D view works best, but plans and sections also work.
‣
Launching the System Inspector
Select any element that belongs to the duct system: a duct, fitting, or air terminal.
If the selection doesn't work, use Tab to cycle until the whole system highlights, then click to select it.
On the Modify | Duct Systems contextual tab, click System Inspector.
In the inspector panel that appears, click Inspect.
‣
Reading the Results
Flow direction arrows appear along the duct network. They show which way air moves through each segment.
Hover over any duct segment or fitting to see a tooltip with:
airflow (CFM) through that segment
static pressure
pressure loss for that segment or fitting
The critical path is highlighted in red. This is the route with the highest total pressure loss, the one that drives fan sizing.
Airflow should accumulate as you move upstream. Branches serving several terminals should carry their combined flow, and the main trunk at the AHU should carry the system total.
‣
What to Look For
Flow totals that don't add up. If a branch carries less air than the terminals it serves, a terminal is probably not connected or is assigned to another system.
Arrows pointing the wrong way. This usually means a misconfigured system classification, an equipment connector set to the wrong flow direction, or no assigned source.
Segments with zero or no data. These are often disconnected stubs or ducts that are in the model but not part of the system.
Unexpectedly high pressure losses. These point to undersized ducts or inefficient fittings, which are worth revisiting during duct sizing.
‣
Making Adjustments
Exit the inspector to make changes. Then re-run it to confirm the results.
Common fixes:
reconnect broken duct runs or fittings.
adjust air terminal flow values.
reassign terminals between systems.
resize ducts or swap fittings along the critical path.
‣
Exiting the System Inspector
Click Finish (or Cancel) on the inspector panel to return to normal editing.
‣
Recommended Workflow
Confirm connectivity with the System Browser first.
Verify that equipment is assigned and calculations are set to All.
Select the system and open the System Inspector.
Click Inspect and trace the flow from the terminals back to the AHU.
Check segment flows, flow direction, and the critical path.
Exit, correct any issues, and re-inspect until the results match your design intent.
Proceed to duct sizing, or refine sizing based on pressure losses.