The Duct Sizing tool automatically resizes duct segments according to the airflow each one carries. It applies the sizing method and constraints you choose. Run it after you've confirmed connectivity and airflow totals with the System Browser and System Inspector.
Workflow
‣
Before You Start
The system must be fully connected. Sizing depends on correct airflow in every segment, and disconnected ducts or terminals give wrong results. Clean these up first with the System Browser and System Inspector.
Air terminal flows must be set. Each diffuser and grille needs its design airflow (CFM). Upstream segments get their flows from these values.
Check that calculations are enabled. In the duct system type properties, the Calculations parameter should be set to All, or at least Flow Only.
Review the available sizes. Go to Manage tab → MEP Settings → Mechanical Settings → Duct Settings. Under Rectangular, Round, and Oval, confirm that the sizes you want are checked as Used in Sizing. The tool only picks from those sizes.
Work on a copy, or save first. Sizing changes many elements at once. Undo works, but a saved fallback is safer.
‣
Using the Duct/Pipe Sizing Tool
‣
Selecting the Ductwork to Size
Hover over a duct in the run you want to size.
Press Tab until the whole run or system highlights, then click to select it.
To size only part of a system, select just those segments and fittings. Use Ctrl to add elements to the selection.
If your selection includes other categories, use Filter to keep only ducts and duct fittings.
On the contextual tab, click Duct/Pipe Sizing in the Analysis panel.
‣
Choosing the Sizing Method
In the Duct Sizing dialog, set how sizes are calculated:
Friction: sizes ducts to a target friction rate, such as 0.08 in. wg per 100 ft.
Velocity: sizes ducts to a target maximum velocity, such as 1,000 FPM for branches.
Combining the two:
Only: uses a single criterion.
And: the duct must satisfy both criteria. This gives more conservative, larger ducts.
Or: the duct must satisfy at least one criterion.
Calculation approach: choose Equal Friction or Static Regain, where those options are available.
‣
Setting Constraints
Branch Sizing controls how branch ducts relate to the terminals they connect to:
Calculated Size Only: sizes branches purely from airflow.
Match Connector Size: keeps branches at the terminal's connector size.
Larger of Connector and Calculated: uses whichever is bigger. This is a common safe choice.
Restrict Height / Restrict Width: caps the dimensions of rectangular ducts. Use this to keep ducts within ceiling plenum depth or joist spaces.
‣
Running the Tool
Click OK. Revit resizes the selected ducts and updates the connecting fittings to match.
‣
Reviewing the Results
Re-run the System Inspector. Confirm that pressure losses along the critical path are reasonable and that no segment has an unexpectedly high loss.
Check for coordination problems. Larger ducts may now clash with structure, ceilings, or other services.
Look for awkward transitions. Sizing can create many small size changes along a run. Consolidate them where a simpler, constant size is more practical to fabricate.
Spot-check segment sizes. Select individual ducts and verify their size, airflow, and velocity in Properties.
Fix any failed connections. Occasionally a fitting can't adapt to new sizes and the connection breaks. Reconnect it and re-check the system.
Recommended Workflow
Confirm connectivity and airflow totals with the System Browser and System Inspector.
Verify the terminal airflows, the calculations setting, and the available duct sizes.
Select the duct run or system using Tab, filtering if needed.
Open Duct/Pipe Sizing, then choose a method and constraints.
Run the tool.
Re-inspect with the System Inspector and check for clashes, awkward transitions, and broken connections.
Make manual adjustments, then re-run sizing on specific runs if needed.