The System Browser gives you a tabular view of every piping component in the model and how each one ties into a system. Before you size pipes, use it to confirm everything is connected as intended and that flows add up correctly.
Workflow
‣
Opening the System Browser
Press F9, or go to View tab → User Interface → System Browser.
It opens as a dockable pane. Widen it so you can see all the columns.
Keep a 3D view of your piping open beside it, zoomed to fit. That way you can see which components you're inspecting.
‣
Setting Up the View
Use the filters at the top to show Systems .
Set the discipline filter to Piping. You can also show All to see how equipment connects across disciplines.
Expand the tree to see the hierarchy: system classification (e.g., Hydronic Supply, Hydronic Return, Domestic Cold Water, Domestic Hot Water, Sanitary, Fire Protection), then each named system, then the individual components.
‣
Reading the Information
Each component row shows key data such as flow, size, and the associated space. For plumbing fixtures, flows are driven by fixture units.
Select any row to highlight that element in the model. For example:
Selecting one fixture or terminal unit shows exactly where it sits.
Selecting a whole system, such as a hydronic supply loop or a domestic cold water system, highlights everything in it. This makes gaps or stray components easy to spot.
‣
Testing How Loads Roll Up
Change a flow value on a component, such as a coil's flow or a fixture's flow. Watch the system total update in the browser.
Set the value back when you're done.
Use this to:
confirm totals match your design intent.
reallocate components between systems if needed.
If totals don't roll up the way you expect, something probably isn't connected the way you think. That might be a broken pipe connection, a fitting that didn't join, or a component assigned to the wrong system.
‣
Understanding the "Unassigned" Section
Any component with a pipe connector that isn't part of a system appears under Unassigned.
This isn't always an error. Equipment often has several connectors across disciplines. For example:
A boiler or chiller might be fully connected on the hydronic side but still show unassigned for its condensate drain, gas supply, or power connection.
An air handler connected to hydronic supply and return may still list unassigned duct or electrical connectors.
These are fine if you simply haven't modeled those connections.
A plumbing fixture, valve, or piece of equipment that should be in a system but appears here usually means a missed connection. Fix it before you move on.
Recommended Workflow Before Pipe Sizing
Open the System Browser and filter to Piping.
Click through each system and confirm its highlighted extent in 3D matches what you expect.
Check that flow totals per system are reasonable.
Review the Unassigned section. Separate intentionally unmodeled connectors from real disconnections.
Fix any connection problems. Then proceed to pipe sizing.