Example: Placing Electrical Equipment / Power Panels
Videos
Workflow
Step 1: Load MEP Versions of Component Families
Library > Electrical > MEP > Electric Power > Distribution
Lighting and Appliance Panelboard
208V or 480V
MCB (miniature circuit breaker) or MLO (main lug only — no breaker)
Surface-mounted or Inset
Step 2: Place Components
Switch to Power Plan views
Place Panelboard(s)
Systems > Electrical > Electrical Equipment
Choose Component from Type Selector
Size (Max Capacity)
Placement Options
Place on Vertical Face
Place on Face
Place on Work Plane
Set Elevation from Level
Electrical equipment consists of panels and transformers. Electrical equipment can be hosted components (an electrical panel that must be placed on a wall), or unhosted (a transformer that can be placed anywhere in a view).
‣
Place a Power Panel
In the Project Browser, expand Views (all)Floor Plans, and double-click the view where you want to place the equipment.
Click Systems tab> Electrical panel > Electrical Equipment.
In the Type Selector, select a component type.
On the ribbon, verify that Tag on Placement is selected to tag the equipment automatically.
On the Options Bar, to include a tag leader, select Leader and specify the length.
The equipment is previewed as you move the cursor over a valid location in the drawing area.
Click to place the equipment.
‣
Select a Distribution System
Electrical panels and transformers that are added in your electrical design must be configured for a distribution system before they can be used with circuits.
In the Project Browser, expand View (all) > Floor Plans, and double-click the plan containing the panel or transformer.
In the drawing area, select a panel, and on the Options Bar, click the Distribution System drop-down, and select a distribution system.
The list contains all of the available distribution systems that match the voltage specification of the panel or transformer, ordered according to distance from the load (closest at the top).