Module 7 Template

Link to Student
Submitted For
Module 7 - Comfort Zone

Working links to all three models in Forma Data Management and your Forma Board

Architectural Model: https://acc.autodesk.com/docs/files/projects/f33d74cd-07ad-475e-a8a8-30d6964935aa?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.tdpO5Tb6SlyWeo0XNQIj4A&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3ALKFL9H1bQDqlaEdyNzRDFA&viewModel=detail&moduleId=folders

Structural Model: https://acc.autodesk.com/docs/files/projects/f33d74cd-07ad-475e-a8a8-30d6964935aa?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.tdpO5Tb6SlyWeo0XNQIj4A&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3AHE-SBwXcRia_zfB-NNGw9A&viewModel=detail&moduleId=folders

Mechanical Model: https://acc.autodesk.com/docs/files/projects/f33d74cd-07ad-475e-a8a8-30d6964935aa?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.tdpO5Tb6SlyWeo0XNQIj4A&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3ADR79dcCpS5qXJvlCCRrVRw&viewModel=detail&moduleId=folders

Forma Board: CEE 220A Forma Boards - Fall 26 - CEE 120A_220A - Zhu - Autodesk Forma Board

PDF sheet set at E1 size, 30 by 42 inches

Module_7_Mech.pdf372 KiB

Load summary table: floor total and by zone

Floor
Zones
Area (ft²)
People
Cooling Total (Btu/h)
Cooling (tons)
Heating (Btu/h)
Cooling (Btu/h·ft²)
Heating (Btu/h·ft²)
Level 0 (0xx)
19
22,176
257
194,063
16.2
161,573
8.8
7.3
Level 1 (1xx – Typical Floor)
28
13,239
217
162,165
13.5
20,664
12.2
1.6
Level 2 (2xx)
29
12,149
216
185,713
15.5
70,326
15.3
5.8
Level 3 (3xx)
29
13,329
215
194,915
16.2
73,040
14.6
5.5
Level 4 (4xx)
29
13,346
215
194,162
16.2
79,943
14.5
6.0
Level 5 (5xx)
29
13,337
196
189,962
15.8
169,254
14.2
12.7
BUILDING TOTAL
163
87,576
1,316
1,120,979
93.4
574,800
12.8
6.6

Load summary by zone for typical floor (i.e. Level 1):

Module7_Load_Summary_by_Floor_and_Zone.xlsx32 KiB

Alternatives comparison: your representative unit and your alternative unit, compared by numbers, with your conclusion

Metric
Representative Unit (Room 110)
Alternative Unit (Room 111)
Total duct length
24.95 ft
41.79 ft
Duct segments
5
5
Longest segment
10' - 1 1/8”
18' - 5 13/16”
Largest duct size after sizing
9" × 9”
9" × 9”
Highest branch velocity
441 FPM
441 FPM
Ducts crossing the rated corridor wall
0
2

Comparing the two rooms, Room 111 needs 41.79 ft of duct to deliver that air versus 24.95 ft for Room 110. This is approximately 16.8 ft (67%) more for the same five segments. Additionally, the longest segment for Room 111 is 18' - 5 13/16", compared with 10' - 1 1/8" for Room 110. The extra length means ducting material and labor is required, leading to increased friction losses. In additional, longer ducts mean more surface area for heat gain and air leakage, decreasing energy efficiency of the HVAC system.

Design memo of 300 to 500 words: your strategy and why, what the loads told you about your envelope, where your structure got in the way, and what you left unresolved

Design Strategy:

The project is located in Sunnyvale California, which falls under CEC Climate Zone 4 (ASHRAE 3C). Due to the mild climate, cooling loads are relatively low, making passive measures extremely effective; this location is slightly heating-dominated by degree days (~2,600 HDD vs. ~200–600 CDD). The psychrometric analysis shows that only 9.2% of annual hours fall within the comfort zone without help. With internal heat gains (39.9%) and passive solar direct gain with high mass (30.1%) added, 97.6% of hours (8,546 of 8,760) can be comfortable. Mechanical heating is needed for about 22.9% of hours and cooling with dehumidification for about 10.0%

Solar heating loads were reduced first via smaller windows on the east and west facades, an overhang on the south side, a cool roof, and exposed concrete slabs for thermal mass on the ground floor. Each perimeter zone on the upper office floors ventilates via a dedicated outdoor air system. Mechanical heating and cooling is provided via a central air-to-water heat pump system, located on the roof. Internal heat gains help supply a significant amount of heating in the building. Hydronic piping and DOAS supply and exhaust ducts rise from the roof through the central mechanical shaft (Room 115), next to the elevator core. The ducts and pipes run on each floor in the plenum along the corridors to fan coil units (FCUs) and ceiling diffusers. Zones were set based on each space’s orientation and use type (i.e. single-orientation zones, corner units, and corridors were separate zones).

The two representative units on a typical floor were selected as follow:

  • Meeting room facing north (Room 110) for the single-zone
  • Kitchen (Room 106) for the multi-zone (split into two as the room wraps a corner)

The alternative unit was chosen to be the meeting room next to Room 110 (i.e. Room 111). The alternative configuration uses a fan coil unit in the hallway instead of locating it in the room.

When assigning space types, occupancy values were adjusted for certain space types. For example, for the kitchen/break room, the space type assigned was ‘dining room.’ However, this resulted in an unreasonable occupancy of around 250 people. Occupancy was changed to ~65 sq ft per person, in accordance with typical commercial guidelines.

From the load analysis, the roof is the primarily source of heat loss across the envelope, likely due to the material properties used in Revit. The cooling loads of the building are primarily driven by internal loads, not the envelope, therefore, focused should be placed on reducing heat gains from internal loads if the design is looking to reduce its cooling loads.

In general, most of the ducts and HVAC equipment were placed around the structural system to prevent clashes. However, in certain areas (i.e. meeting rooms were space was tight), some of the ducts connecting the diffusers to the air terminal overlapped with previously placed beams. The structural system should be re-looked at, to see whether it’s possible to remove these beams and replace with a different form of structural support in these rooms. However, this was left unresolved due to time constraints.

Climate Consultant Chart for Sunnyvale, CA

image