Working links to all three models in Forma Data Management and your Forma Board
Architectural Model: https://acc.autodesk.com/docs/files/projects/1a04a1ba-5c7b-4227-9d7f-06b66256ebf9?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.kIXddjbwRg6g7gi41jqJCg&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3ADetGnZv8SKWJGPFd0Yfe7Q&viewModel=detail&moduleId=folders
Structural Model: https://acc.autodesk.com/docs/files/projects/1a04a1ba-5c7b-4227-9d7f-06b66256ebf9?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.BHTd25r7SCWZKbPS9W_FOg&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3A7MLTlMUQRo2Ip8WmRqBK1g&viewModel=detail&moduleId=folders
Mechanical: https://acc.autodesk.com/docs/files/projects/1a04a1ba-5c7b-4227-9d7f-06b66256ebf9?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.7yh2ybQaQmSWiHoXdTjNAQ&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3At97RuAyFS5int7JU9OZxkw&viewModel=detail&moduleId=folders
Forma Board: Module 7 - Fall 26 - CEE 120A_220A - Adelekan - Autodesk Forma Board
PDF sheet set at E1 size, 30 by 42 inches
Please paste your PDF sheet set here…
Load summary table: floor total and by zone
Please paste your load summary table here…
Alternatives comparison: your representative unit and your alternative unit, compared by numbers, with your conclusion
Please paste your two alternatives comparison here, what differs between them, and which you choose and why…
Design memo of 300 to 500 words: your strategy and why, what the loads told you about your envelope, where your structure got in the way, and what you left unresolved
My design strategy: My building is based in Napa California near the Napa River. Napa is quite mild all year round. It experiences long, warm dry summers and mild, wet winters.
Climate Consultant shows only 8% of annual hours are comfortable with no form of heating/cooling. Additionally, it shows that heating is the highest need with 32% of annual hours needing active heating to achieve comfort. Since most annuals appear on the left, it shows those hours are too cold and heating should be the focus,
My goal was to be able to achieve the most occupant comfort with the least complex HVAC design. The chart’s best strategies were passive solar direct gain, internal heat gain from residents and appliances, window shading, night flushing, and active heating.
Climate Consultant Chart from Napa, California

I aim to use windows and overhangs to block heat in the summer and allow in heat in the winter to passively heat building. I also think the stack effect of my building will help heating. I aim to place a distributed heat pump for all the rooms on each floor using the consistent mech shaft placement. Californian buildings are required to use solar PVs so I will place PVs on my roofs to generate electricity for building and the elelctric heat pump. The building is near a semi major street so I will opt to deliver air using an ERV so that I can still get ventilation if it is impossible to open windows for ventilation. Diffusers will deliver air to rooms as it is compact and is on the ceiling so it doesnt affect the user spaceI will also assume that noise in the night will be minimal so night flushing can still occur. I will also aim to install some noise screens
What Claude is saying - 13th November 2026
My building is an 8-story, roughly 80,000 sf residential project in Napa, California, near the Napa River (Climate Zone 02). Napa has long, warm, dry summers and mild, wet winters. Climate Consultant shows only 8.1% of annual hours are comfortable with no strategy, and active heating is the biggest need at 32% of hours. Passive strategies cover much of the rest: internal heat gain from residents and appliances (30.7%), passive solar direct gain with high mass (27.3%), sun shading of windows (15.3%) and night-flushed thermal mass (11.9%). Together these reach 99.9% comfort in the chart, which I treat as a best case.
My goal is the most comfort with the least complex HVAC. I will use an airtight, well-insulated envelope, overhangs and shading sized by orientation, and exposed thermal mass. I will not rely on stack effect, since in an 8-story building it mostly drives leakage. For ventilation, I will use an ERV in each apartment, because street noise and wildfire smoke may make open windows impractical. Night flushing through operable windows is a bonus, not something I depend on.
For heating and cooling, I will use distributed reversible air-source heat pumps: a ducted fan coil in each unit, each with its own roof condenser. Heating drives the sizing, and cooling covers hot afternoons. Air is delivered through ceiling diffusers, which are compact and keep the occupied space clear. Rooftop PV will offset part of the electric load.
I will model my typical floor, Level 1. I will zone it with one System-Zone per unit, split into separate zones by orientation for corner units, plus one for the corridor. My two representative units are 102, the 1-bedroom, as the single-zone unit, and 101, the 2-bedroom, as the multi-zone unit, split into [two] zones by orientation. My alternative is 111, the twin of 102 across the corridor, with [the fan coil in the corridor ceiling instead of inside the unit]. Everything else in the twin stays the same, so the comparison isolates that one change.
One zone is assigned for each standard unit as they experience the sun from the same direction so they can use the same heating and cooling load. Corner units are split into two zones by orientation as they experience the sun from two different directions so they will require different cooling and heating loads