- Working links to all five models in Forma Data Management (architectural, structural, mechanical, plumbing and electrical) and your Individual Forma Board.
- PDF sheet set at E1 size, 30 by 42 inches, four sheets: plumbing plan, riser section showing the sanitary fall, power plan, lighting plan.
- Your illumination spot check result.
- Design memo of 300 to 500 words: where the sanitary riser went and why, what gravity forced you to change, whether your daylighting reduced your lighting load, and what you left unresolved.
Working links to all five models in Forma Data Management (architectural, structural, mechanical, plumbing and electrical) and your Individual Forma Board
https://acc.autodesk.com/docs/files/projects/38e8ef54-de0a-406a-9432-e675869106c9?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.V9H_Lhz5Tr6kWNF-VCH0RA&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3ALXk3XXijQ9OuvDHqUd53oQ&viewModel=detail&moduleId=folders https://acc.autodesk.com/docs/files/projects/38e8ef54-de0a-406a-9432-e675869106c9?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.V9H_Lhz5Tr6kWNF-VCH0RA&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3AFoLUQVSXSm-_ySTbSBThMw&viewModel=detail&moduleId=folders https://acc.autodesk.com/docs/files/projects/38e8ef54-de0a-406a-9432-e675869106c9?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.V9H_Lhz5Tr6kWNF-VCH0RA&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3AAopgkMSoRJWMyMhlBfu4FQ&viewModel=detail&moduleId=folders https://acc.autodesk.com/docs/files/projects/38e8ef54-de0a-406a-9432-e675869106c9?folderUrn=urn%3Aadsk.wipprod%3Afs.folder%3Aco.V9H_Lhz5Tr6kWNF-VCH0RA&entityId=urn%3Aadsk.wipprod%3Adm.lineage%3AaHl-X4oTQz6Z4MmKJWwTiA&viewModel=detail&moduleId=folders https://app.autodeskforma.com/board/up_eo2no9k0o4/board_b7457c75-e96b-4907-95a4-d8c643920922?x=2528.1184284977226&y=537.8457997881096&w=4648.378378378378&h=2520.2432432432433
PDF sheet set at E1 size, 30 by 42 inches, four sheets: plumbing plan, riser section showing the sanitary fall, power plan, lighting plan
Your illumination spot check result
Level 2 dormitory room - Room 1 (Living Quarters β Dormitory) The estimated average illumination at a 2'-6" workplane is about 380 lx (35.3 fc) from 2 recessed 2x4 LED lights (96 VA each, 192 VA total, or 0.94 VA/SF), using standard ceiling, wall, and floor reflectances of 75%, 50%, and 20%. Since Revit's Space tool showed Not Computed because of the linked architectural ceiling, I calculated this number from the light's Revit specs of 8,550 lumens each and a 0.88 light loss factor. The target for general lighting in a residential dorm is about 100 to 200 lx (10 to 20 fc), so 380 lx is brighter than needed because I used commercial 96 W office lights, removing 1 light (which brings the room to about 190 lx) or switching to smaller residential lights would put it right in the target range.
Design memo of 300 to 500 words: where the sanitary riser went and why, what gravity forced you to change, whether your daylighting reduced your lighting load, and what you left unresolved
For the representative area, I placed the main vertical sanitary riser along the interior wall directly behind the restroom water closets and lavatory sinks. Locating the stack along this interior restroom wall kept the horizontal waste branch runs short, preserved clear floor space inside the restroom, and kept the plumbing core away from exterior walls, structural columns, and the corridor wall where the electrical panelboard was mounted. Because sanitary drainage relies on gravity rather than water pressure, I had to model all horizontal waste branches with a continuous downward slope toward the main stack. That slope forced me to drop the elevation of the waste lines gradually along their runs and route them underneath the flat, pressurized cold and hot water supply pipes so the two systems would not collide at the same height. I also had to extend vertical vent piping upward above the fixtures to keep air pressure balanced and protect the trap seals. Daylighting did not reduce the connected electrical lighting load. Even though the bedrooms have exterior windows, I controlled the rooms with standard single-pole manual switches rather than automated daylight dimming sensors, so the lights still draw their full connected load (768 VA across my eight 2x4 fixtures) whenever turned on. However, replacing the two commercial troffers in each dorm room with a single fixture or adding daylight controls would easily cut that lighting load in half. Finally, a few items were left unresolved for future full-building modeling. Rather than modeling full systems across every floor I limited my electrical branch circuits to the representative Level 2 zone and restricted my plumbing layout to a single stacked vertical core spanning the three residential floors. In addition, I left the Week 7 Air Handling Unit completely uncircuited and disconnected from my local 208V lighting panel, and left the linked architectural ceiling boundaries uncomputed for Revit's automatic space illumination engine.