Module 8 Template

Link to Student
Submitted For
Module 8 - Wired and Plumbed

Working links to all five models in Forma Data Management (architectural, structural, mechanical, plumbing and electrical) and your Individual Forma Board

ARCH

STRUCTURAL

MECH

PLUMB

ELECTRICAL

PDF sheet set at E1 size, 30 by 42 inches, four sheets: plumbing plan, riser section showing the sanitary fall, power plan, lighting plan

*note this is only 2 sheets as Cesar put both plumbing and riser, onto one sheet along with power and lighting onto one sheet, therefore I did the same.

HUNT-PLUMB-buildingM8.pdf181.1 KiB
HUNT-ELECTRICAL-buildingM8.pdf149.1 KiB

Your illumination spot check result

image

Design memo of 300 to 500 words: where the sanitary riser went and why, what gravity forced you to change, whether your daylighting reduced your lighting load, and what you left unresolved

Sanitary riser. I placed the 4" sanitary stack at the east end of the building, about 107 ft east of the project origin. The 1" hot and cold water risers run beside it, and a 2" vent runs up to the roof at 36 ft. I stacked these in one wet wall from Level 0 through Level 3 so each floor's fixtures can reach them with short horizontal branches. It also keeps the plumbing away from the west wing, where the mechanical equipment and ductwork sit.

What gravity forced. Drainage is the one system that can't be routed freely, because waste has to fall continuously. At the base of the stack, the 4" sanitary line turns horizontal about 2 ft below the Level 1 floor, at roughly 4 ft elevation, in the plenum above the commercial level. Gravity made me move my toilet by a few inches. The water lines were easier to work with since they could bend around obstacles.

Daylighting. Revit's illumination check ignores daylight, so my spot check against the 30 to 50 foot-candle office target reflects electric light only. My Week 4 analysis showed evidence of daylight in both bedrooms and the living room, but not substantial amounts. Due to this, I would not have lowered the design illumination level in those rooms, because the target has to hold when daylight is absent, such as in the evening. I would, however, choose different fixtures that allow dimming, so the lighting can drop when daylight is strong. That would cut the energy load without changing the design level.

What I left unresolved.

  • Dimming. I have not yet selected or modeled dimmable fixtures or the controls that would pair with them.
  • Mechanical coverage. Only one unit has flex ducts, so my electrical connection to the fan coil unit applies to that zone only.