Module 8 Template

Link to Student
Submitted For
Module 8 - Wired and Plumbed
💡

Please enter the following info in the fields above:

  • Link to Student (type the first few letter of your name, then select yourself in the list of linked records)
💡

What to Submit

  1. Working links to all five models in Forma Data Management (architectural, structural, mechanical, plumbing and electrical) and your Individual Forma Board.
  2. PDF sheet set at E1 size, 30 by 42 inches, four sheets: plumbing plan, riser section showing the sanitary fall, power plan, lighting plan.
  3. Your illumination spot check result.
  4. Design memo of 300 to 500 words: where the sanitary riser went and why, what gravity forced you to change, whether your daylighting reduced your lighting load, and what you left unresolved.

Working links to all five models in Forma Data Management (architectural, structural, mechanical, plumbing and electrical) and your Individual Forma Board

Arch

Struc

Mech

Plum

Elec

Forma Board

PDF sheet set at E1 size, 30 by 42 inches, four sheets: plumbing plan, riser section showing the sanitary fall, power plan, lighting plan

Tran-Drawings-Week8.pdf2.9 MiB

Your illumination spot check result

This is a living room/kitchen/dining room. The average expected luminance is 229 lx and considering the different spaces, the typical min would be 100 lx and the max would be 400 lx, so it’s in a good middle ground.

image

Design memo of 300 to 500 words: where the sanitary riser went and why, what gravity forced you to change, whether your daylighting reduced your lighting load, and what you left unresolved

image

Apparent power is voltage times current, so the panel can carry 100 A times 208 V. This is 20,800 VA. The load is approximately 1900 VA which which is only about a tenth of the panel capacity. A 100 A panel is adequate, with a lot of capacity left for any future renovations.

I put the sanitary riser inside the west wall, on the center of the wall, a little over three and a half feet north of the room corner. I chose that wall because the shower backs onto it, and the toilet and lavatory face other walls, so no single wall could serve all three. A concrete beam blocks the first foot of the wall and joists cross it at two spots, and the toilet drain needs a long straight run, so I pushed the riser further north. Gravity decided the order of the pipes. The sanitary line is the lowest lane, drains run from the fixture down to the riser, and the riser ends in a short trunk at the bottom. I hung the lanes under the joists so they wouldn't run into them. I didn't slope the drains because it was not required, so they are flat in my model. I didn’t do any daylighting analysis in this module, so I don't know how well it reduced the lighting load. I’m not fully sure if it was included in the luminance, but considering that I had to add an extra light where the restroom’s window is to meet typical luminance, I presume it didn’t affect the lighting. Therefore in real life, the rooms with windows would be brighter than designed for. Some unresolved things include the unsloped drains, the panel not showing where the power comes from, and the toilet and lavatory vents ending in the wall.